How Many Fire Extinguishers Do You Need? Placement, Spacing and Mounting Height

Brian Story, Co-founder of AED Log

By Brian Story

Co-founder, AED Log

Updated November 22, 2026 · 7 min read

Most buildings need enough fire extinguishers that nobody is ever more than 75 feet from one, and at least one on every floor. How many that adds up to depends on your floor area, how much can burn there, and the rating of the extinguishers you buy. NFPA 10, the national standard for portable fire extinguishers, turns that into a simple calculation, and OSHA sets the walking distances for workplaces.

Here’s how to work out the number for your building, where each extinguisher should go, and how high to mount it.

Does your business need fire extinguishers?

Almost certainly. OSHA’s rule for general industry tells employers to provide portable fire extinguishers and to mount, place and mark them so employees can reach them easily without putting themselves at risk. State and local fire codes can require them too, so check with your fire marshal or fire extinguisher service company.

OSHA allows one narrow exception. A workplace can go without extinguishers only if a written fire safety policy sends everyone out immediately when the alarm sounds, the employer has a written emergency action plan and fire prevention plan, no extinguishers are kept there, and no other OSHA standard calls for one. If a written emergency action plan names the only employees allowed to use the extinguishers and has everyone else in the area leave when the alarm sounds, OSHA’s spacing rules below don’t apply, but its inspection and maintenance rules still do.

If you do provide extinguishers for employees to use, OSHA also requires training on how to use them when someone is hired and at least once a year after that. Our free emergency action plan template covers the written emergency action plan.

How many fire extinguishers do I need?

Divide each floor’s area by the area one extinguisher can cover, round up, then add extinguishers wherever someone would be more than 75 feet from one. NFPA 10 works it out in four steps:

  1. Rate the hazard. Light hazard covers places like offices, classrooms, churches, assembly halls and hotel guest rooms. Ordinary hazard covers places like dining areas, shops and their storage rooms, light manufacturing, workshops and auto showrooms. Extra hazard covers places like woodworking shops, vehicle repair, parking garages, cooking areas and spaces where flammable liquids are handled.
  2. Look up how much area one extinguisher covers. It depends on the number in front of the A on the extinguisher’s label (its Class A rating) and on the hazard, up to a limit of 11,250 square feet per extinguisher.
  3. Divide and round up. Divide each floor’s area by that figure. A floor smaller than one extinguisher’s area still needs one.
  4. Check the walking distance. Walk the floor: no spot should be more than 75 feet from an extinguisher, measured along the route a person would actually walk. If the layout needs more extinguishers than the math, add them.
Floor area one Class A fire extinguisher covers, by hazard (NFPA 10)
Extinguisher rating Light hazard Ordinary hazard Extra hazard
2-A 6,000 sq ft 3,000 sq ft Not enough (4-A minimum)
3-A 9,000 sq ft 4,500 sq ft Not enough (4-A minimum)
4-A 11,250 sq ft 6,000 sq ft 4,000 sq ft
6-A 11,250 sq ft 9,000 sq ft 6,000 sq ft
10-A 11,250 sq ft 11,250 sq ft 10,000 sq ft

Two examples: a 15,000 square foot office floor (light hazard) protected with 2-A extinguishers needs at least 3 (15,000 ÷ 6,000 = 2.5, rounded up). The same size of workshop (ordinary hazard) needs at least 5 with 2-A extinguishers, or 3 with 4-A extinguishers. In both cases, check the 75-foot walk next, because a long or broken-up floor can need more.

Areas with flammable liquids, energized electrical equipment, combustible metals or commercial cooking need extinguishers made for those fires too, placed by the rules below.

Fire extinguisher placement requirements

Put extinguishers where people already walk, in plain sight, and close enough to the hazard they cover. The maximum walking distance depends on the kind of fire:

Maximum walking distance to a fire extinguisher, by class of fire (OSHA 29 CFR 1910.157 and NFPA 10)
Class of fire What burns Maximum walking distance
Class A Wood, paper, cloth, trash, plastics 75 feet
Class B Flammable liquids and gases 50 feet under OSHA; 30 or 50 feet under NFPA 10, depending on the hazard and the extinguisher’s B rating
Class C Fires involving energized electrical equipment Placed like the Class A or B extinguishers for the area
Class D Combustible metals 75 feet
Class K Cooking oils and fats in commercial kitchens 30 feet (NFPA 10)

NFPA 10 adds a few placement rules of its own:

  • Along normal paths of travel, including the way out of each area, so people grab an extinguisher on their way to the exit.
  • Visible and easy to reach, with nothing stacked in front of it. Where something unavoidably blocks the view, a sign has to show where it is.
  • Mounted properly: on the hanger or bracket made for it, or in a cabinet or wall recess. Extinguishers in vehicles, or anywhere they could be knocked loose, go in strap-type brackets.
  • Protected where they could be hit, shaken or damaged by the conditions around them.

OSHA’s rule says employees must be able to reach extinguishers “without subjecting the employees to possible injury,” so place them where getting one doesn’t mean going past the hazard.

Fire extinguisher mounting height

For most extinguishers, the top should be no more than 5 feet above the floor. NFPA 10 sets three limits:

  • 40 pounds or less (gross weight, which covers most hand-held extinguishers): top no higher than 5 feet.
  • Over 40 pounds (except wheeled units): top no higher than 3½ feet.
  • Every hand-held extinguisher: at least 4 inches between its bottom and the floor.

An extinguisher in a cabinet or wall recess must still meet the same heights. Where the ADA applies, mind the walkway as well: under the 2010 ADA Standards, a wall-mounted object whose leading edge sits between 27 and 80 inches above the floor can stick out no more than 4 inches into a walkway.

Fire extinguisher sign requirements

An extinguisher that can be seen needs no sign; one that can’t be seen does. NFPA 10 calls for signs or other markers wherever something blocks the view of an extinguisher, including one inside a cabinet that isn’t visible. The sign goes right next to the extinguisher, where people walking by on the usual route can see it. OSHA’s rule also asks employers to identify extinguishers so employees can find them.

Fire extinguisher rules for construction sites

Construction sites follow their own OSHA rule, with a simpler formula. Under 29 CFR 1926.150, a jobsite needs an extinguisher rated at least 2-A for every 3,000 square feet of the building, or the larger part of that, with no point more than 100 feet from one. Every floor needs at least one 2-A extinguisher, and in a building with several floors at least one has to sit next to a stairway. Wherever more than 5 gallons of flammable or combustible liquid, or 5 pounds of flammable gas, is in use, an extinguisher rated at least 10-B has to be within 50 feet. See AED and safety equipment tracking for manufacturing and construction.

How AED Log keeps track of every extinguisher

Once you know how many extinguishers you need and where, AED Log keeps them inspected. Each extinguisher gets a record at its location, with its class and rating, and a QR code label that opens it on any phone. The monthly checklist asks whether it’s accessible and unobstructed, whether the gauge is in the green, whether the pin and tamper seal are intact, and whether there’s any damage, and every inspection is saved with the date and the inspector’s name.

Each extinguisher’s next service and hydrostatic test due dates show on the compliance calendar and raise an alert before they’re due. Every plan includes unlimited locations, and fire extinguishers are an add-on at $6 per extinguisher per year, on top of an AED plan. See fire extinguisher inspection software, Brian’s guide to fire extinguisher inspection requirements, and how long fire extinguishers last. Replacing old ones? Here’s how to dispose of a fire extinguisher.

Fire extinguisher placement FAQ

How many fire extinguishers does a small business need?

At least one on every floor, and enough that nobody is more than 75 feet from one. In a light-hazard office, one 2-A extinguisher covers up to 6,000 sq ft, so a 4,000 sq ft single-floor office needs one if every spot is within that 75-foot walk.

How far apart should fire extinguishers be?

Close enough that the walk to the nearest one is no more than 75 feet for ordinary combustibles. Under OSHA, it’s 50 feet from areas with flammable liquids; under NFPA 10, it’s 30 feet from commercial cooking equipment.

How high should a fire extinguisher be mounted?

For an extinguisher of 40 pounds or less, the top should be no more than 5 feet above the floor; for a heavier one, no more than 3½ feet. Leave at least 4 inches between the bottom and the floor. These are NFPA 10’s limits.

Does OSHA require fire extinguishers?

In almost every workplace, yes. The exception: everyone evacuates at the alarm under written emergency action and fire prevention plans, no extinguishers are kept there, and no other OSHA standard calls for one.

Do fire extinguishers need signs?

Only when they can’t be seen. NFPA 10 requires a sign or other marker near any extinguisher hidden from view, such as one in a closed cabinet, placed next to it where people walking by can see it.

Can AED Log track fire extinguishers by location?

Yes. Each extinguisher gets a record and a QR code label at its location, with monthly checks on any phone and alerts before its service and hydrostatic test dates. It’s $6 per extinguisher per year on top of an AED plan.